Untitled Document
Untitled Document
หน้าหลัก > Sensors > Hanyoungnux > Temp Controller

Temp Controller

AX Series

- Multi input 
- Multi output 
- High speed sampling cycle (0.1 sec) 
- Installation depth : 63mm 
- Control output selectable : Reverse operation/Direct operation 
- PID auto tuning

*** Download Datasheet ***

Description

Suffix code

Model Code Information
AX  - Digital temperature controller
Dimension 2     AX2 : 48 X 96 mm
3     AX3 : 96 X 48 mm
4     AX4 : 48 X 48 mm
7     AX7 : 72 X 72 mm
9     AX9 : 96 X 96 mm
Output selection 1   SSR + Relay1 + Relay2 Relay or SSR as control output
(selectable in operator setup mode)
2   SSR + Relay1 + Relay2 + Relay3
1B   SSR + Relay1(Form c) + Relay2 Only for AX2, 3, 7, 9
2B   SSR + Relay1(Form c) + Relay2 + Relay3
3   4 - 20 ㎃ + Relay2 Current output as control output
4   4 - 20 ㎃ + Relay2 + Relay3
Power supply voltage A 100 - 240 V a.c 50/60 ㎐
※ Form C : Normal close type contact
※ Relay output operates as control output, alarm output and LBA output depending on the internal parameter setting.

Specification

Appearance AX4 AX3 AX7 AX2 AX9

48 X 48 X 63 96 X 48 X 63 72 X 72 X 63 48 X 96 X 63 96 X 96 X 63
Input type Multi input(Thermocouple : K, J, R, T, IEC 584-1), (RTD : Pt100 Ω, IEC751)
Sampling cycle 100 ms
Input impedance max 1 ㏁
Albwable input wiring resistance 10 V DC
Display accuracy Thermocouple
K,J,T
± 0.3 % of F.S ±1 digit (RJC error ±0.8%) ℃
Thermocouple
R
±1.0% of F.S ±1 digit in the 0 ~ 600 ℃ range

± 2.0℃ in the range of 0~600℃, ± 0.8℃ outside of the range

±0.3 % F.S ±1 digit in the 600 ~ 1700 ℃ range
Pt100 ±0.3 % of F.S ±1 digit℃
Display type 7 Segment LED (PV : red, SV : green)
Font size PV 13.0 X 6.5 15.9 X 7.6 14.5 X 7.0 14.5 X 7.0 22.5 X 11.2
SV 9.2 X 5.2 12.0 X 6.0 9.4 X 4.7 10.8 X 5.2 18.7 X 9.3
Input resolving power
  • • Thermocouple : 0.1℃ (K2, J, T), 0.5℃ (K1), 0.3℃ / 1℉ (R)
  • • RTD : 0.03℃, (0.1 ℉)
Insulation resistance min 20㏁, 500 V DC 1 minute (primary terminal - secondary terminal)
Dielectric strength 2,300 V AC, 50/60 ㎐, for 1min (primary terminal - secondary terminal)
Control method PID control by Auto-tuning, ON/OFF control
Manual reset Users set with in the range 0.0% - 100.0%
Control output operation Reverse operation / Direct operation selectable by the parameter setting
Control output
  • • Relay output ※Selectable by the prameter setting 1a contact,
    3 A 240 V AC, 3 A 30 V DC(resistive load)
  • • Voltage pluse output for running SSR [time sharing proportional control (CYC)]
  • • Voltage plus output for running SSR [phase control(PHR)] 0/12 V DC, pulse voltage
    (resistive load minimum 600Ω)
4 - 20 ㎃ DC(resistive load max. 600Ω)
Power supply voltage 100 - 240 V AC 50 / 60 ㎐
Voltage fluctuation ±10 % of the power supply voltage
Power consumption 5.5 VA max
Ambient temperature -5 ~ 50℃
Ambient humidity 35 ~ 85% RH (without condensation)
Vibration resistance 10 -55 ㎐, 0.75 mm, each to direction, X, Y and Z for 2 hours
Shock resistance 300 ㎨ to direction 6 each 3 times
Weight 180 g 320 g 300 g 320 g 400g

HX Series

- Installation Depth 63 ㎜
- Fast Sampling Cycle 62.5 ㎳
- Multi-Input·Multi-Output
- Communication (RS485, RS422)
- Heating Control / Cooling Control /Simultaneous Heating ∙ Cooling Control
- Heater Break Alarm . Reternsmission Output
- Setting Value (SV) Selection by Contact Input (D.I)

*** Download Datasheet ***

Description

Suffix code

Model Code Information
HX -
Multi-input and output digital temperature controller
Dimension 2     48(W) X 96(H) mm P.I.D Auto-tuning
3     96(W) X 48(H) mm
4     48(W) X 48(H) mm
7     72(W) X 72(H) mm
9     96(W) X 96(H) mm
Control output 0   Normal (heating control)
1   Heating/cooling control (simultaneous control)
HX2/3/9 option 0 None
1 RS485 communication + Heater break alarm (H.B.A)
HX7 option 0 None
1 RS485 communication + D.I 2 contacts (SV2, SV3)
2 RS485 communication + Heater break alarm (H.B.A)
HX4 option 0 None
1 RS485 communication + D.I 1 contact (SV2)
2 RS485 communication + Heater break alarm (H.B.A)

Specification

Model HX9 HX7 HX2 HX3 HX4
Appearance
 
 
 
 
W x H x D (㎜) 96 x 96 x 63 48 x 96 x 63 72 x 72 x 63 96 x 48 x 63 48 x 48 x 63
Power supply 100 - 240 V a.c (±10%), 50/60 ㎐
Power consumption 6 W max, 10 VA max
Input Type Refer to "input code for input type and range"
Sampling cycle 62.5 ms
Accuracy ±0.5% of F.S(refer to "input code for input type and range")
Allowable voltage Within ±20 V d.c (VDC), within ±10 V d.c (TC, RTD)
Reference junction compensation accuracy ±3.5℃ (0 ~ 50℃)
Operation after input break T.C : OFF, UP/DOWN RTD : UP
Control
output
Relay NO : 5 A 250 V a.c, 5 A 30 V d.c (resistive load)
NO : 3 A 250 V a.c, 1 A 30 V d.c (resistive load)
S.S.R(voltage pulse) ON voltage : 12 V d.c min, OFF voltage : 0.1 V d.c max
Load resistance 600 Ω min
S.C.R(current) range : 4 - 20 mA (±5%), accuracy : ±0.2 mA
Load resistance 600 Ω max
Retransmission output range : 4 - 20 mA (±5%), accuracy : ±0.2 mA
Load resistance 600 Ω max
Alarm output 5 A 250 V a.c, 5 A 30V d.c (resistive load)
Contact input OFF resistance : 10 ㏀ min, ON resistance : 1 ㏀ max
Control Method ON/OFF, P.I.D control
Output operation Reverse operation, Direct operation
Anti-reset windup Auto(A=0), 0.1 ~ 100.0 %
Interface Standard EIA RS 485
Max connection unit 31 units (but, ADDRESS setting : 1 ~ 99)
Communication method 2 wire half duplex
Data transmission asynchronous
Communication sequence None
Communication distance 1.2 km max
Communication Speed 2400, 4800, 9600, 14400, 19600 BPS (selectable by parameter)
Start bit 1 BIT
Data length 7 or 8 BIT
Parity bit NONE, EVEN, ODD
Stop bit 1 or 2 BIT
Protocol PC.LINK, PC.LINK SUM, MODBUS-ASCII, MODBUS-RTU
Response time Processing time in receiving + (response time X 10 ms)
2 degrees of freedom P.I.D 1 ~ 100% of proportional band
Insulation resistance 20 ㏁ min (primary terminal - secondary terminal)
Dielectric strength 2,300 V a.c, for 1 minute (primary terminal - secondary terminal)
Operating ambient temperature 0 ~ 50℃, (without condensation)
Operating ambient humidity 35 ~ 85% R.H (without condensation)